mge-shut - Driver for SHUT Protocol UPS equipment

Author

       Arnaud Quette

Extra Arguments

       This driver also supports the following optional settings:

       lowbatt=num
           Set the low battery warning threshold at which shutdown is initiated by upsmon(8).

           The factory default value is 30 (in percent), and can be settable depending on the exact model.

       offdelay=num
           Set the timer before the UPS is turned off after the kill power command is sent (via the -k switch).

           The default value is 20 (in seconds). Usually this mustbelower than ondelay, but the driver will
           not warn you upon startup if it isn’t.

       ondelay=num
           Set the timer for the UPS to switch on in case the power returns after the kill power command had
           been sent but before the actual switch off. This ensures the machines connected to the UPS are, in
           all cases, rebooted after a power failure.

           The default value is 30 (in seconds). Usually this mustbegreater than offdelay, but the driver will
           not warn you upon startup if it isn’t. Some UPSes will restart no matter what, even if the power is
           (still) out at the moment this timer elapses. In that case, you could try if setting ondelay=-1 in
           ups.conf helps.

               Warning
               ondelay parameter was set in ten seconds unit in the legacy mge-shut driver ( 3 for 30 seconds) .
               It is now set in seconds ( 30 for 30 seconds). Make sure you use the correct unit in your
               configuration.

       notification=num
           Set notification type to 1 (no), 2 (light) or 3 (yes).

           This argument is ignored. It is only here for backward compatibility.

Known Issues

Repetitivetimeoutandstaleness
       Some models tend to be unresponsive with the default polling frequency. The result is that you have some
       "data stale" errors in your system log.

       In this case, simply modify the general parameter pollinterval to a higher value (like 10 for 10
       seconds). This should solve the issue.

       Using notification=3 might also help.

Name

       mge-shut - Driver for SHUT Protocol UPS equipment

See Also

Thecoredrivernutupsdrv(8)

   Internetresources
       The NUT (Network UPS Tools) home page: https://www.networkupstools.org/historic/v2.8.3/

Network UPS Tools 2.8.3                            07/08/2025                                        MGE-SHUT(8)

Supported Hardware

       mge-shut supports all recent Eaton, MGE and Dell UPS models which use the SHUT (Serial HID UPS Transfer)
       protocol.

       Older MGE models, such as Pulsar ESV+, Pulsar EX and Pulsar ES+, use the U-Talk protocol and should use
       the mge-utalk driver.

Synopsis

mge-shut -h

       mge-shut -a UPS_NAME [OPTIONS]

           Note

           This man page only documents the hardware-specific features of the mge-shut driver. For information
           about the core driver, see nutupsdrv(8).