Set out below is a sample of the status output which may be generated for the specified UPS models.
Allmodels
APC : version, number of records and number of bytes following
DATE : Date and time of last update from UPS
HOSTNAME : hostname of computer running apcupsd
VERSION : apcupsd version number, date and operating system
UPSNAME : UPS name from configuration file (dumb) or EEPROM (smart)
CABLE : Cable type specified in the configuration file
MODEL : UPS model derived from UPS information
UPSMODE : Mode in which UPS is operating
STARTTIME : Date and time apcupsd was started
STATUS : UPS status. One or more of the following (space-separated): CAL TRIM BOOST ONLINE ONBATT
OVERLOAD LOWBATT REPLACEBATT NOBATT SLAVE SLAVEDOWN
or
COMMLOST
or
SHUTTING DOWN
MASTERUPD : Last time the master sent an update to the slave
ENDAPC : Date and time of status information was written
Smart-UPSandMatrix-UPS(SmartSignalling)
LINEV : Current input line voltage
LOADPCT : Percentage of UPS load capacity used as estimated by UPS
BCHARGE : Current battery capacity charge percentage
TIMELEFT : Remaining runtime left on battery as estimated by the UPS
MBATTCHG : Min battery charge % (BCHARGE) required for system shutdown
MINTIMEL : Min battery runtime (MINUTES) required for system shutdown
MAXTIME : Max battery runtime (TIMEOUT) after which system is shutdown
MAXLINEV : Maximum input line voltage since apcupsd started
MINLINEV : Min (observed) input line voltage since apcupsd started
OUTPUTV : Current UPS output voltage
SENSE : Current UPS sensitivity setting for voltage fluctuations
DWAKE : Time UPS waits after power off when the power is restored
DSHUTD : Delay before UPS powers down after command received
DLOWBATT : Low battery signal sent when this much runtime remains
LOTRANS : Input line voltage below which UPS will switch to battery
HITRANS : Input line voltage above which UPS will switch to battery
RETPCT : Battery charge % required after power off to restore power
ITEMP : UPS internal temperature in degrees Celcius
ALARMDEL : Delay period before UPS starts sounding alarm
BATTV : Current battery voltage
LINEFREQ : Current line frequency in Hertz
LASTXFER : Reason for last transfer to battery since apcupsd startup
NUMXFERS : Number of transfers to battery since apcupsd startup
XONBATT : Date, time of last transfer to battery since apcupsd startup
TONBATT : Seconds currently on battery
CUMONBATT : Cumulative seconds on battery since apcupsd startup
XOFFBAT : Date, time of last transfer off battery since apcupsd startup
SELFTEST : Date and time of last self test since apcupsd startup
STESTI : Self-test interval
STATFLAG : UPS status flag in hex
DIPSW : Current UPS DIP switch settings
REG1 : Fault register 1 in hex
REG2 : Fault register 2 in hex
REG3 : Fault register 3 in hex
MANDATE : UPS date of manufacture
SERIALNO : UPS serial number
BATTDATE : Date battery last replaced (if set)
NOMOUTV : Nominal output voltage to supply when on battery power
NOMBATTV : Nominal battery voltage
EXTBATTS : Number of external batteries (for XL models)
BADBATTS : Number of bad external battery packs (for XL models)
FIRMWARE : UPS firmware version
APCMODEL : APC model information
NewerBack-UPSPro(SmartSignalling)
LINEV : Current input line voltage
LOADPCT : Percentage of UPS load capacity used
MBATTCHG : Min battery charge % (BCHARGE) required for system shutdown
MINTIMEL : Min battery runtime (MINUTES) required for system shutdown
MAXTIME : Max battery runtime (TIMEOUT) after which system is shutdown
MAXLINEV : Maximum input line voltage since apcupsd startup
MINLINEV : Minimum input line voltage since apcupsd startup
OUTPUTV : Current UPS output voltage
BATTV : Current battery charge voltage
STATFLAG : UPS status flag in hex
Back-UPSRS1500(USB)
LINEV : Current input line voltage
LOADPCT : Percentage of UPS load capacity used
BCHARGE : Current battery capacity charge percentage
TIMELEFT : Remaining runtime left on battery as estimated by UPS
MBATTCHG : Min battery charge % (BCHARGE) required for system shutdown
MINTIMEL : Min battery runtime (MINUTES) required for system shutdown
MAXTIME : Max battery runtime (TIMEOUT) after which system is shutdown
*OUTPUTV : Current UPS output voltage
*DWAKE : Time UPS waits after power off when the power is restored
*DSHUTD : Delay before UPS powers down after command received
LOTRANS : Input line voltage below which UPS will switch to battery
HITRANS : Input line voltage above which UPS will switch to battery
*RETPCT : Battery charge % required after power off to restore power
*ITEMP : UPS internal temperature in degrees Celcius
ALARMDEL : Delay period before UPS starts sounding alarm
BATTV : Current battery voltage
*LINEFREQ : Current line frequency in Hertz
*LASTXFER : Reason for last transfer to battery since apcupsd startup
NUMXFERS : Number of transfers to battery since apcupsd startup
XONBATT : Date, time of last transfer to battery since apcupsd startup
TONBATT : Seconds currently on battery
CUMONBATT : Cumulative seconds on battery since apcupsd startup
XOFFBAT : Date, time of last transfer off battery since apcupsd startup
SELFTEST : Date and time of last self test since apcupsd startup
STATFLAG : UPS status flag in hex
MANDATE : UPS date of manufacture
SERIALNO : UPS serial number
BATTDATE : Date battery last replaced (if set)
NOMBATTV : Nominal battery voltage
FIRMWARE : UPS firmware version
APCMODEL : APC model information
* presence dependent on USB firmware version.
Web/SNMP(AP9716)orPowerNetSNMP(AP9605)SmartSlotCard
LINEV : Current input line voltage
LOADPCT : Percentage of UPS load capacity used as estimated by UPS
BCHARGE : Current battery capacity charge percentage
TIMELEFT : Remaining runtime left on battery as estimated by UPS
MBATTCHG : Min battery charge % (BCHARGE) required for system shutdown
MINTIMEL : Min battery runtime (MINUTES) required for system shutdown
MAXTIME : Max battery runtime (TIMEOUT) after which system is shutdown
MAXLINEV : Maximum input line voltage since apcupsd startup
MINLINEV : Minimum input line voltage since apcupsd startup
OUTPUTV : UPS output voltage
SENSE : Current UPS sensitivity setting for voltage fluctuations
DWAKE : Time UPS waits after power off when the power is restored
DSHUTD : Delay before UPS powers down after command received
DLOWBATT : Low battery signal sent when this much runtime remains
LOTRANS : Input line voltage below which UPS will switch to battery
HITRANS : Input line voltage above which UPS will switch to battery
RETPCT : Battery charge % required after power off to restore power
ITEMP : UPS internal temperature in degrees Celcius
ALARMDEL : Delay period before UPS starts sounding alarm
LINEFREQ : Current line frequency in Hertz
NUMXFERS : Number of transfers to battery since apcupsd startup
TONBATT : Seconds currently on battery
CUMONBATT : Cumulative seconds on battery since apcupsd startup
XOFFBATT : Date, time of last transfer off battery since apcupsd startup
STESTI : Self-test interval
STATFLAG : UPS status flag in hex
DIPSW : Current UPS DIP switch settings
MANDATE : UPS date of manufacture
SERIALNO : UPS serial number
BATTDATE : Date battery last replaced (if set)
NOMOUTV : Nominal output voltage to supply when on battery power
NOMPOWER : Nominal power output in watts
EXTBATTS : Number of external batteries (for XL models)
BADBATTS : Number of bad external battery packs (for XL models)
FIRMWARE : UPS firmware version
APCMODEL : APC model information
Share-UPS(AP9270)(Basicport)
MBATTCHG : Min battery charge % (BCHARGE) required for system shutdown
MINTIMEL : Min battery runtime (MINUTES) required for system shutdown
MAXTIME : Max battery runtime (TIMEOUT) after which system is shutdown
NUMXFERS : Number of transfers to battery since apcupsd startup
TONBATT : Seconds currently on battery
CUMONBATT : Cumulative seconds on battery since apcupsd startup
XOFFBATT : Date, time of last transfer off battery since apcupsd startup
STATFLAG : UPS status flag in hex
UPSEnvironmentalMonitoringSmartSlotCard(AP9612TH)
HUMIDITY : Ambient humidity
AMBTEMP : Ambient temperature
Back-UPSProandSmart-UPSv/s(SmartSignalling)
LINEFAIL : Input line voltage status.
BATTSTAT : Battery status.
LASTXFER : Last (observed) transfer to battery.
Back-UPSandNet-UPS(SimpleSignalling)
LINEFAIL : Input line voltage status.
BATTSTAT : Battery status.
STATFLAG : UPS status flag in hex.