liebert-esp2 - Driver for Liebert UPS, using the ESP-II serial protocol
Contents
Extra Arguments
This driver supports the following optional settings in ups.conf(5):
baudrate=num
Set the speed of the serial connection — 1200, 2400 (default), 4800, 9600 or 19200.
Name
liebert-esp2 - Driver for Liebert UPS, using the ESP-II serial protocol
See Also
Thecoredriver:nutupsdrv(8) Internetresources: The NUT (Network UPS Tools) home page: https://www.networkupstools.org/historic/v2.8.3/ Network UPS Tools 2.8.3 07/08/2025 LIEBERT-ESP2(8)
Special Cabling Note
Be aware that an RS-232 cable with ONLY the RX, TX and ground pin must be used when interfacing with GXT2
series UPS units (and possibly others), since the handshaking lines are used for purposes other than
RS-232 flow control.
Use of a standard RS-232 cable with full handshaking may result in undesired operation and/or shutdown.
It is therefore advisable to confirm the proper cable/wiring with the diagram provided in the manual with
your UPS.
Supported Hardware
Tested to work on the following units:
• Liebert GXT2-6000RT208
This is an experimental driver. You have been warned.
This driver currently does not support modification of configuration parameters, such as the low battery
warning time and automatic restart policy.
Synopsis
liebert-esp2 -h
liebert-esp2 -a UPS_NAME [OPTIONS]
Note
This man page only documents the hardware-specific features of the liebert-esp2 driver. For
information about the core driver, see nutupsdrv(8).