px2_configure - deploy and configure Raritan PX2/PX3 power distribution units
Contents
Arguments
LIST
Device list in CSV format.
IPS Device IP addresses; use 'all' to run on all IPs in the CSV file.
IP Device IP address.
OUTFILE
Output file name.
IMAGE
Firmware image file.
TZID
Timezone ID as printed by the "print_timezones" command.
Commands
configureLISTIPS
Configure some or all devices (network settings, unit name and SNMP settings).
The behavior of this command is different depending on whether concrete IP addresses or the 'all'
keyword is specified:
• If IP addresses are specified the program will contact each device, read its serial number and
search for a matching entry in the device list. It will then change the device's network settings
to the values from the device list. The initial IP addresses do not have to match the values from
the device list, they might as well be dynamically assigned by a DHCP server.
• If the 'all' keyword is specified the IP addresses are taken from the device list. The devices'
network settings are expected to be properly configured at this point, so the network configuration
part will be skipped.
verifyLISTIPS
Verify device settings and SNMP access.
identifyLISTIPS
Identify some or all devices (show a distinctive string for two seconds in each unit's display).
rebootLISTIPS
Reboot some or all devices.
fetch_fitnessLISTOUTFILEIPS
Fetch fitness data from some or all devices and write them to a file in CSV format.
updateLISTIMAGEIPS
Device firmware update. The firmware image will be sequentially uploaded to each device, then all
devices will be instructed to perform the firmware update in parallel.
print_timezonesIP
Print list of supported timezones with its IDs.
set_timezoneLISTTZIDIPS
Set the timezone of all devices.
Description
PX2 deployment and configuration utility.
Device List Format
The device list file contains a list of PX2 devices in CSV format. It could e.g. be exported from an
inventory spreadsheet. Each device line contains four or five fields, separated by commas:
1. Unit serial number (exactly 10 characters)
2. PDU name
3. IP address with prefix length (e.g. 192.168.99.1/24)
4. Gateway IP address
5. Optional comment; the line is ignored if "ignore" is included here
Lines with less than four fields are silently ignored. Likewise, lines that do not contain a valid serial
number are disregarded.
Examples
px2_configureconfiguredevices.csv192.168.2.3
Connect to the device at 192.168.2.3, read its serial number and look it up in the device list file
named devices.csv. Configure the device's network, PDU name and SNMP settings.
px2_configureverifydevices.csvall
Verify the network settings, PDU name and SNMP access for all devices in the list file.
px2_configureupdatedevices.csvpdu-px2-020106-26030.binall
Update all devices to firmware version 2.1.6.
Name
px2_configure - deploy and configure Raritan PX2/PX3 power distribution units
Requirements
The following Perl modules are required to run this script:
• Raritan PX2 RPC bindings (distributed along with this script)
• libwww-perl <https://metacpan.org/release/libwww-perl>
• LWP::Protocol::https <https://metacpan.org/release/LWP-Protocol-https>
• JSON <https://metacpan.org/release/JSON>
• JSON-RPC-Common <https://metacpan.org/release/JSON-RPC-Common>
• perl-Error <https://metacpan.org/release/Error>
• Test-Simple <https://metacpan.org/release/Test-Simple>
Additionally, the verify command uses the snmpget utility to verify SNMP access.
perl v5.40.0 2024-11-17 px2_configure(1p)
Synopsis
px2_configure COMMAND [ARGUMENTS]